01A service is a set of measurements, not a wipe-down
Filter cleaning and a coil rinse are the visible part. A service worth paying for also records supply and return air temperatures, refrigerant pressures, electrical draw, drain condition and the physical state of coils, insulation and mountings. Those numbers are how you tell whether performance is drifting before it fails.
02Monthly, by you
- Clean or wash the indoor filters (more often if you are near the beach or have pets)
- Check the outdoor unit is clear of leaves, sand, grass clippings and stored items
- Look for water under the indoor unit or staining on the wall
- Listen for new rattles, humming or clicking at start-up
03Every six months near the coast
For equipment within a few hundred metres of the water, or on an exposed roof, a six-monthly visit is the sensible baseline. It should include a proper coil clean on both sides, a drain flush and trap check, an electrical inspection of terminals and contactors, refrigerant pressure and temperature readings, and a look at brackets, insulation and pipe lagging.
04Annually, everywhere
Further inland, or on a sheltered property, an annual service covers the same checklist. Whatever the interval, the visit should end with a written record of what was measured, so next year's technician is comparing against something.
05Commercial equipment runs a different schedule
Busy kitchens, delis and retail floors should be on a three to six-month cycle. Grease and salt together form a film on condenser coils that insulates them and pushes head pressure up, which costs electricity and shortens compressor life. Restaurants near the harbour are at the hard end of that range.
06Signs you have left it too long
- Rooms take noticeably longer to reach temperature than they used to
- The unit runs constantly and the electricity bill has crept up
- Water drips from the indoor unit or the drain outlet is dry
- A musty smell returns within days of cleaning the filters
- Ice on the indoor coil or the copper pipes
- Visible fin loss, rust or white powder on the outdoor coil